Sale!
	
	
	
	
		
					
				
	
			
					
				
	
			
			
		
			
	
	
			Description
Specifications
OVERVIEW
| UPC Code | 037332177933 | 
| UPS Type | On-Line | 
INPUT
| Rated input current (Maximum Load) | Hardwire AC input: 24.2A (220V), 21.7A (230V), 22.2A (240V) maximum; Max inrush current: 100A | 
| Nominal Input Voltage(s) Supported | 220V AC; 230V AC; 240V AC | 
| Nominal Input Voltage Description | 230V factory default | 
| UPS Input Connection Type | Hardwire | 
| UPS Input Connection Description | Hardwire input supports 3 wire L, N, PE(GND) International wiring configurations only | 
| Input Phase | Single-Phase | 
| Input Frequency | 50 / 60 Hz | 
| Power Factor (Input) | 0.98 minimum (full load, nominal input voltage) | 
| THDi | <8% full load; <10% half load | 
OUTPUT
| Output Volt Amp Capacity (VA) | 5000 | 
| Output Capacity (kVA) | 5 | 
| Output Watt Capacity (Watts) | 5000 | 
| Output kW Capacity (kW) | 5 | 
| Output Capacity Details | Inverter supports up to 104% load continuously, Up to 125% / 150% for 1.0 / 0.5 min. before bypass transfer (when available) or shutdown; Loads greater than 150% trigger immediate shutdown; AC TRANSIENT RESPONSE: ±1.5% RMS of initial value (between 10% & 90% load step) | 
| Power Factor | 1.0 | 
| Crest Factor | 3:1 maximum | 
| Nominal Voltage Details | Nominal output voltage selection is available via front panel LCD interface; 220/230/240v recommended | 
| Frequency Compatibility | 50 / 60 Hz | 
| Frequency Compatibility Details | MAX-QUALITY/MAX-EFFICIENCY/AUTO-ADAPTIVE MODES: Output frequency matches input nominal on startup and tracks input frequency up to ±3Hz of nominal; When input frequency is greater than ±3Hz of nominal, output frequency is inverter regulated to ±0.5Hz of nominal; BATTERY MODE: Output frequency is inverter regulated to ±0.5Hz of the configured nominal output frequency; FREQUENCY CONVERSION MODE: Output is inverter regulated to the selected 50/60Hz output setting with ±0.5Hz regulation (de-rates to 70% capacity, bypass not available); FREQUENCY REGULATION MODE: Enables frequency correction to ±0.5Hz of the frequency sensed by the UPS on startup (no de-rating, bypass is available when input frequency is within ±0.5Hz of output) | 
| Load Management Receptacles | Two built-in switchable output load banks; BANK 1 (Set of 2 C19 outlets); BANK 2 (Set of 6 C13 outlets) | 
| Output Circuit Breakers | Two 16A single-pole breakers protect 2 C19 outlets each; 10A single-pole breaker protects 6 C13 outlets | 
| Output AC Waveform (AC Mode) | Pure Sine wave | 
| Output AC Waveform (Battery Mode) | Pure Sine wave | 
| Nominal Output Voltage(s) Supported | 200V; 208V; 220V; 230V; 240V | 
| Output Receptacles | (6) C13; (4) C19; Hardwire | 
| Output Voltage Regulation | ±1% Inverter output; ±10% Economy mode; ±15% Bypass mode (configurable from ±5% to ±20%); Output voltage THD <2% (full load) / <3% (half load) | 
| Individually Controllable Load Banks | Yes | 
BATTERY
| Battery Type | Valve Regulated Lead Acid (VRLA) | 
| Full Load Runtime (min.) | 5 minutes (5000 watts) | 
| Half Load Runtime (min.) | 14 minutes (2500 watts) | 
| Expandable Battery Runtime | Runtime is expandable with external battery packs | 
| Expandable Runtime | Yes | 
| Expandable Runtime Description | Up to 4 external battery packs with sensor cabling are automatically sensed and configured for advanced temperature controlled charging and accurate runtime reporting; Configurations using 5-10 external battery packs are supported, but may require the use of Tripp Lite’s EXTERNAL BATTERY CONFIGURATION software for for full integration | 
| External Battery Pack Compatibility | BP192V12RT3US | 
| DC System Voltage (VDC) | 192 | 
| Battery Recharge Rate (Included Batteries) | 3 hours from 10% to 90% (typical, internal batteries with full load discharge); Charge settings: 1.5A (internal batteries) / 2A (with external battery packs) configures automatically; Supports temperature compensated battery charging | 
| Battery Access | Front panel battery access door | 
| Internal UPS Replacement Battery Cartridge | RBC58-3US (qty 1) | 
| Battery Replacement Description | Hot-swappable, user replaceable internal batteries and external battery packs | 
VOLTAGE REGULATION
| Voltage Regulation Description | ±1% Inverter output regulation; ±10% in optional Eco mode | 
| Overvoltage Correction | Corrects overvoltages as high as 275V | 
| Undervoltage Correction | Corrects undervoltages as low as 156V (100% load) / 100V (50% load); derates linearly | 
USER INTERFACE, ALERTS & CONTROLS
| Front Panel LCD Display | Selectable LCD display with Escape, Page Up, Page Down, Enter and Power buttons enable UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats (see manual) | 
| Switches | Includes main power off/on switch, plus Up, Down, Enter and Esc switches to set and execute LCD functions. | 
| Alarm Cancel Operation | Alarm cancel switch | 
| Audible Alarm | Unique audible alarms for all major UPS, environmental and power conditions (see manual) | 
| LED Indicators | 4 front-panel LEDs indicate AC input, AC output, Battery mode and Fault conditions | 
SURGE / NOISE SUPPRESSION
| UPS AC Suppression Joule Rating | 1680 | 
| UPS AC Suppression Response Time | Instantaneous | 
| EMI / RFI AC Noise Suppression | Yes | 
PHYSICAL
| Primary Form Factor | Rackmount | 
| Rack Height | 3U | 
| Cooling Method | Load and thermal controlled cooling fans; Field-replaceable (92mm x 38mm, ball-bearing, 115 CFM) | 
| Included Mounting Accessory Description | Includes 4 post rackmount installation accessories; Included mounting brackets support front-to-rear rail distances of 520 to 914.4mm (20.5 to 36 in.); Enclosures require a minimum depth of 780 mm (30.7 in.) from the front rails to the closed rear door | 
| Installation Form Factors Supported with Included Accessories | 4 post 19 inch rackmount | 
| Installation Form Factors Supported with Optional Accessories | 2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND ) | 
| Minimum Required Rack Depth (inches) | 32 | 
| Primary UPS Depth (mm) | 762 | 
| Primary UPS Height (mm) | 131 | 
| Primary UPS Width (mm) | 445 | 
| Shipping Dimensions (hwd / in.) | 6.89 x 23.70 x 33.35 | 
| Unit Dimension Details | Minimum required rack depth assumes 127mm / 5 in. additional depth for AC input/output cabling; See submittal drawing for additional dimension detail | 
| UPS Housing Material | Sheet metal | 
| UPS Power Module Dimensions (hwd, in.) | 5.14 x 17.5 x 30 | 
| UPS Power Module Weight (kg) | 53.30 | 
| UPS Power Module Weight (lbs.) | 117.5 | 
ENVIRONMENTAL
| Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius | 
| Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius | 
| Relative Humidity | 5 to 95%, non-condensing | 
| AC Mode BTU / Hr. (Full Load) | 1050 | 
| AC Mode Efficiency Rating (100% Load) | >94% | 
| AC Economy Mode Efficiency Rating (100% Load) | >98% | 
| Operating Elevation (ft.) | Up to 6562 ft. | 
| Audible Noise | 67.1dB (full load) / 53dB (no load) front side 1m | 
| Operating Elevation (m) | Up to 2000m | 
COMMUNICATIONS
| Network Management Cards | WEBCARDLXMINI | 
| Network Monitoring Port Description | Includes Pre-installed WEBCARDLXMINI network management card; DB9 port supports RS-232 and Contact-closure signaling | 
| PowerAlert Software | For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert | 
| Communications Cable | USB, DB9 serial and EPO cables included | 
| WatchDog Compatibility | Yes | 
| Network Management Card Description | Network management card included | 
| Communications Interface | Contact closure; DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface; USB (HID enabled) | 
LINE / BATTERY TRANSFER
| Transfer Time | Online to Battery mode: 0 ms. (Zero transfer time) | 
| Transfer Time (Economy Mode) | Online to Eco mode: 2 milliseconds / Eco to Battery mode: 8 milliseconds | 
| Low Voltage Transfer to Battery Power (Setpoint) | 156V (full load) / 100V (50% load or less, derates linearly) | 
| High Voltage Transfer to Battery Power (Setpoint) | 275V | 
FEATURES & SPECIFICATIONS
| Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | 
| High Availability UPS Features | Auto Probe Monitoring and Reboot (requires WEBCARDLXMINI); Automatic inverter bypass; Hot swappable batteries; On-Line/Double-Conversion; Surge/noise protection; Zero transfer time | 
| Green Energy-Saving Features | High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation; Support for daily startup and shutoff | 
STANDARDS & COMPLIANCE
| Product Compliance | RoHS; CE (Europe); ENERGY STAR Qualified; FCC Part 15 Class A (USA) | 
WARRANTY & SUPPORT
| Product Warranty Period (Worldwide) | 2-year limited warranty | 
Additional information
| Weight | 74.16 kg | 
|---|---|
| Dimensions | 17.5 × 60.19 × 84.7 cm | 
| Brand | 