Description
Specifications
OVERVIEW
| UPC Code | 037332141071 |
INPUT
| Nominal Input Voltage(s) Supported | 230V AC |
| Recommended Electrical Service | DC INPUT: Requires 24VDC input source capable of delivering 145A for the required duration (when used at full continuous capacity – DC requirements increase during OverPower and DoubleBoost operation). |
| Maximum Input Amps | 28 |
| Input Connection Type | DC INPUT: Set of DC bolt-down terminals. AC INPUT: Hardwire via built in terminal strip with cover plate |
| Voltage Compatibility (VAC) | 230 |
| Voltage Compatibility (VDC) | 24 |
OUTPUT
| Frequency Compatibility | 50 / 60 Hz |
| Frequency Compatibility Details | 50 or 60 Hz (user-selectable) |
| Pure Sine Wave Output | Yes |
| Output (Watts) | 3000 |
| Nominal Output Voltage(s) Supported | 230V |
| Output Receptacles | Hardwire |
| Continuous Output Capacity (Watts) | 3000 |
| Peak Output Capacity (Watts) | 6000 |
| Output Voltage Regulation | LINE POWER (AC): Maintains 230V nominal sine wave output from line power source. INVERTER POWER (AC): Maintains sine wave output voltage of 230 VAC (+/-5%). |
| Output Frequency Regulation | 50/60 Hz (+/- 0.3 Hz) |
BATTERY
| Expandable Battery Runtime | Runtime is expandable with any number of user supplied wet or gel type batteries |
| Expandable Runtime | Yes |
| DC System Voltage (VDC) | 24 |
| Battery Pack Accessory (Optional) | 98-121 sealed lead acid battery (optional) |
| Battery Charge | Selectable 23 / 90 amp |
VOLTAGE REGULATION
| Voltage Regulation Description | Includes automatic voltage regulation to correct brownouts and overvoltages back to usable levels |
| Overvoltage Correction | Overvoltages are automatically reduced by 10% |
| Brownout Correction | Brownouts are automatically boosted by 10% and 20% |
USER INTERFACE, ALERTS & CONTROLS
| Front Panel LEDs | Set of 6 LEDs offer continuous status information on load percentage (6 levels reported) and battery charge level (7 levels reported). See manual for sequences. |
| Switches | 3 position on/off/remote switch enables simple on/off power control plus “auto/remote” setting that enables distant on/off control of the inverter system when used in conjunction with optional APSRM4 accessory when used in inverter mode. In AC uninterrupt |
PHYSICAL
| Material of Construction | Metal |
| Cooling Method | Fan |
| Shipping Dimensions (hwd / in.) | 20.08 x 18.43 x 22.52 |
| Shipping Weight (lbs.) | 87.00 |
| Unit Dimensions (hwd / in.) | 10.08 x 8.90 x 12.40 |
| Unit Weight (lbs.) | 64.8 |
ENVIRONMENTAL
| Relative Humidity | 0-95% non-condensing |
| Operating Temperature | 32-104 Fahrenheit / 0-40 Celcius |
LINE / BATTERY TRANSFER
| Transfer Time (Line Power to Battery Mode) | Dip-switch selectable 20 millisecond (full cycle) / 10 millisecond (half-cycle) transfer times which are compatible with many computers, servers and networking equipment – verify transfer time compatibility of loads for UPS applications |
| Low Voltage Transfer to Battery Power | In 230V AC “auto” mode, inverter/charger switches to battery mode as line voltage drops to 170V AC (user adjustable to 180V). |
| High Voltage Transfer to Battery Power | In 230V AC “auto” mode, inverter/charger switches to battery mode as line voltage increases to 260V (user adjustable to 270 – see manual). |
FEATURES & SPECIFICATIONS
| TVSS Grounding | Main grounding lug connects inverter/charger to earth or vehicle chassis ground |
STANDARDS & COMPLIANCE
| Product Certifications | UL 1741 |
| Product Compliance | RoHS |
WARRANTY & SUPPORT
| Product Warranty Period (U.S. & Canada) | 2-year limited warranty |
Additional information
| Weight | 39.46 kg |
|---|---|
| Dimensions | 51 × 46.81 × 57.2 cm |
| Brand |