Description

Description
Do you need to protect small- to medium-size servers, networking equipment and telecom systems against data
loss, downtime and equipment damage due to power outages, voltage fluctuations and transient surges? Tripp
Lite’s SU1000XLCD SmartOnline® Tower UPS System is the solution! Featuring a 1000VA/900W capacity and
true on-line operation with pure sine wave output and zero transfer time to battery, it provides the highest level of
power protection for mission-critical equipment. The SU1000XLCD’s large internal battery set supports connected equipment during blackouts, and runtime is
expandable with optional external battery packs (Tripp Lite model BP24V15RT2U, BP24V28-2U or BP24V70-3U), sold separately. The SU1000XLCD has 6
5-15R outlets, including 2 single-outlet load banks that are individually controllable to reboot select equipment on demand or maximize battery runtime for
mission-critical equipment. USB and DB9 communication ports support messaging of detailed UPS operational parameters and line power status. PowerAlert
UPS management software is available via free download. It comes backed by$250,000 of Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only).
Features
Ideal for Protection of Mission-Critical Equipment
The SU1000XLCD provides true on-line operation, reliable battery backup and comprehensive power management capability in a compact tower form factor.
Featuring a 1000VA/900W capacity, 6 5-15R outlets, a 10-ft. cord with standard 5-15P plug, USB/DB9 ports and a slot for an optional network management
accessory card, the SU1000XLCD offers a complete power protection solution for small- to medium-size servers, storage devices, telecom systems and other
mission-critical equipment.
True On-Line Operation with Pure Sine Wave Output and Zero Transfer Time
The SU1000XLCD provides the highest level of protection available for mission-critical equipment. It actively converts raw incoming AC power to DC, then
re-converts it back to regulated, filtered AC output with a pure sine wave, completely isolating connected components from all power problems. Zero transfer
time between AC and battery operation maintains continuous output and further protects connected equipment from the disruptive effects of blackouts and
severe low-voltage conditions. Sine wave output guarantees compatibility with all equipment types.
Individually Controllable Outlets
Highlights
1000VA / 1kVA / 900 watt on-line
double-conversion tower UPS
100/110/120/127V 50/60Hz
output, high efficiency economy
mode option
Interactive LCD with 10
selectable screens of UPS and
site power data
Expandable runtime,
Hot-swappable batteries
USB, RS232 & EPO ports,
Network Management Card
options
2 independently switched load
banks
NEMA 5-15P input; 6 5-15R
outlets
Package Includes
SU1000XLCD SmartOnline®
Tower UPS System
USB, DB9 and EPO Cables
Owner’s Manual
1 / 6
The SU1000XLCD includes 2 single-outlet load banks that are individually controllable via a software interface for remote reboot of locked-up equipment or
load shedding to maximize battery backup time for mission-critical equipment.
Reliable, Expandable Battery Backup
UPS battery backup keeps connected equipment operational through short power failures, and provides time to save data and perform an orderly system
shutdown in case of a prolonged blackout. The SU1000XLCD features a large internal battery set that provides 12.8 minutes of battery support for a half load
(450 watts) and 3.8 minutes for a full load (900 watts). Intelligent battery management system extends battery life. During normal operation, incoming utility
power keeps the UPS battery fully charged so that backup power will always be available if needed. For mission-critical applications demanding continuous
uptime, the fully scalable SU1000XLCD can provide expandable runtime with optional external battery packs (Tripp Lite model BP24V15RT2U, BP24V28-2U or
BP24V70-3U), sold separately.
High Power Factor and Highly Efficient Operation Reduces BTU Output
The SU1000XLCD features a high 0.9 power factor and an optional, highly efficient economy mode setting that can significantly reduce a facility’s energy
costs. In economy mode, the UPS operates with 96% efficiency, minimizing heat output, reducing cooling requirements and consuming less electricity.
AC Line and Tel/Ethernet Surge Suppression
A sudden power surge or spike can damage or destroy electronic components and wipe out irreplaceable data. The SU1000XLCD features a 570-joule surge
suppression rating to protect connected components and data from the harmful effects of power surges. One set of tel/Ethernet (RJ45) jacks provides surge
protection for a standard phone or network connection (cable not included).
EMI/RFI Line Noise Filtering
Various electrical and radio sources can cause disruptive interference on the AC line. This line noise is a common cause of incremental hardware damage,
data corruption and audio/video performance problems. The SU1000XLCD incorporates technology that filters out disruptive line noise, preventing it from
affecting your equipment.
LCD Screen and Audible Alarm
The SU1000XLCD features a front-panel LCD screen that enables IT personnel to monitor line power, on-line mode, bypass mode, on-battery, overload,
battery low, replace battery and fault status information. It is supplemented by an audible alarm that signals UPS startup, power failure, low battery, overload,
UPS fault and remote shutdown conditions.
USB/DB9 Ports, Network Management Cards and PowerAlert Software
SU1000XLCD includes HID-compliant USB interface that enables integration with built-in power management and auto shutdown features of Windows and
Mac OS X. USB and DB9 ports enable data-saving unattended shutdown when used with Tripp Lite’s PowerAlert software, available via FREE download from
www.tripplite.com/poweralert. Compatible with Tripp Lite UPS management card options TLNETCARD, WEBCARDLX, SNMPWEBCARD, MODBUSCARD and
RELAYIOCARD.
Emergency Power Off (EPO) Capability
The SU1000XLCD features an EPO interface port that supports emergency shutoff in large facilities (cable included).
Peace of Mind
The SU1000XLCD comes with$250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only) for connected equipment.
Specifications
2 / 6
OUTPUT
Output Volt Amp Capacity (VA) 1000
Output kVA Capacity (kVA) 1
Output Watt Capacity (Watts) 900
Output kW Capacity (kW) 0.9
Output Capacity Details
ON LINE MODE: Maximum output capacity rating is reduced to 810W at 100V nominal; FREQUENCY
REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion
mode (127/120/115/110V 630 watts / 100V 567 watts) OVERLOAD CAPACITY: Supports inverter operation up to
105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds
before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN
(when bypass input voltage or frequency are OUTSIDE bypass limits)
Power Factor 0.9
Crest Factor 3:1
Nominal Output Voltage(s)
Supported 100V; 110V; 115V; 120V; 127V
Nominal Voltage Details 120V default
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency
when input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
BATTERY MODE: Output is regulated to +/-0.05Hz of selected nominal.
Output Voltage Regulation (Line
Mode) +/- 2%
Output Voltage Regulation
(Economy Line Mode) +/- 10%
Output Voltage Regulation (Battery
Mode) +/- 3%
Output Receptacles (6) 5-15R
Load Management Receptacles Two switchable single-outlet 5-15R load banks
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 10A
Nominal Input Voltage(s) Supported 100V AC; 110V AC; 120V AC; 127V AC
Nominal Input Voltage Description 120V factory default
UPS Input Connection Type 5-15P
Input Circuit Breakers 15A
UPS Input Cord Length (ft.) 10
3 / 6
UPS Input Cord Length (m) 3.0
Recommended Electrical Service 15A 120V
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 3.8 min. (900w)
Half Load Runtime (min.) 12.8 min. (450w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility BP24V15RT2U(limit 1); BP24V28-2U(limit 1); BP24V70-3U(multi-pack compatible)
Expandable Runtime Description External battery configurations require the use of Tripp Lite’s External Battery Configuration Software, see manual
for details
DC System Voltage (VDC) 24
Battery Recharge Rate (Included
Batteries) Less than 3 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge RBC24V-LCD
Battery Access Battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction 2% output voltage regulation during overvoltages to 150
Undervoltage Correction 2% output voltage regulation during undervoltages to 55V (33% load), 70V (70% load), 100V (100% load)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating
data, plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options
Switches 2 switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 570
UPS AC Suppression Response
Time Instantaneous
UPS Dataline Suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC Noise Suppression Yes
4 / 6
PHYSICAL
Primary Form Factor Tower
UPS Power Module Dimensions
(hwd, in.) 10 x 6.8 x 13.2
UPS Power Module Dimensions
(hwd, cm) 25.40 x 17.27 x 33.53
UPS Shipping Dimensions (hwd / in.) 14.2 x 10 x 18.5
UPS Shipping Dimensions (hwd /
cm) 36.07 x 25.40 x 46.99
Cooling Method Fan
UPS Housing Material Steel
Primary UPS Height (mm) 254
Primary UPS Width (mm) 173
Primary UPS Depth (mm) 335
Shipping Height (mm) 361
Shipping Width (mm) 254
Shipping Depth (mm) 470
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 341
AC Economy Mode BTU / Hr. (Full
Load) 128
Battery Mode BTU / Hr. (Full Load) 585
AC Mode Efficiency Rating (100%
Load) 90%
AC Economy Mode Efficiency Rating
(100% Load) 96%
Audible Noise < 50 dB at front side 1m
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network Management Cards SNMPWEBCARD; TLNETCARD; WEBCARDLX; MODBUSCARD; RELAYIOCARD
Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure
communications
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://www.tripplite.com/poweralert
5 / 6
Communications Cable USB and DB9 cabling included
WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time Zero transfer time (0 ms.) in online, double-conversion and frequency regulation / conversion modes;
Low Voltage Transfer to Battery
Power (Setpoint) 55V (33% load), 70V (70% load), 100V (100% load)
High Voltage Transfer to Battery
Power (Setpoint) 150
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure) Cold-start operation supported
High Availability UPS Features Automatic inverter bypass; Hot swappable batteries
Green Energy-Saving Features High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
mode operation
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B (EMI)
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance

Additional information

Weight 15.19 kg
Dimensions 35.3 × 24.89 × 45.72 cm
Brand