SmartOnline 208/240 & 120V 12kVA 8.4kW Double-Conversion UPS, 8U, Extended Run, Network Card Slot, USB, DB9, Bypass, NEMA

Sale!

KShs2,194,935.86

SmartOnline 208/240 & 120V 12kVA 8.4kW Double-Conversion UPS, 8U, Extended Run, Network Card Slot, USB, DB9, Bypass, NEMA

Add to Wishlist
Add to Wishlist
Compare
SKU: SU12000RT4U Category:

Description

SmartOnline 208/240 & 120V 12kVA 8.4kW
Double-Conversion UPS, 8U, Extended Run,
Network Card Slot, USB, DB9, Bypass, NEMA
MODEL NUMBER: SU12000RT4U
Description
Tripp Lite 12kVA SmartOnline Hot-Swappable Modular Rack/Tower UPS offers 12,000 VA on-line,
double-conversion UPS support for server, network and telecommunications equipment. Maintains
battery-derived AC output during blackouts with active, full-time power conditioning. Fault-tolerant auto-bypass
prevents unexpected service interruptions during overload or internal fault conditions. 4U power module and 4U
external battery pack installs in 8 rack spaces (8U). Upright tower installation supported with optional
accessories. Maintains full-time sine wave output within 3% of selectable 208/120 or 240/120V AC. Corrects
brownouts and overvoltages from 65V to 140V (L-N). Expandable runtime with optional external battery packs.
Converts raw input from AC to DC, then resynthesizes output power back to perfect sine wave AC output with
enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems
not addressed by other UPS types. Highly efficient operation in optional economy mode setting, saving BTU heat
output and energy costs. Network-grade AC surge and noise suppression. Network management interfaces include combination DB9 RS-232 enabled and dry
contact serial port, enhanced USB port and slot for network management card options. HID-compliant USB interface enables integration with built-in power
management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and
utility power conditions via all 3 network interfaces. PowerAlert UPS monitoring software is available via free download. Supports Emergency Power Off (EPO)
via built-in interface. Front panel LEDs and LCD readout with scroll controls support visual monitoring of all major UPS functions. LED/LCD display panel easily
rotates for viewing in rackmount or tower configurations. Split phase 4 conductor hardwire input and output supported. UPS supported outlets include two
L6-30R, six C19 and 5 low voltage 5-15/20R. Output connections are mounted on a detachable backplate with manual bypass switch to enable hot-swappable
UPS replacement without powering off connected equipment. External battery packs are field replaceable and hot swappable. Attractive all-black color
scheme. $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only).
Features
True online, double-conversion UPS provides pure, full-time sine wave AC output free of surges, voltage fluctuations and line noise
12,000 VA / 8400 watt output power capacity with dual voltage output of 208/120 or 240/120V
4U high power density power module and 4U external battery pack supports rackmount installation in 8 rack spaces
Highlights
12kVA / 12,000VA / 8400W
on-line double-conversion UPS
208/120V or 240/120V +/-3%
output at 60Hz, 94% Efficient
Economy-mode option
8U Rack / Tower compatible;
Hot-swappable power and
battery modules
USB, RS232 & EPO ports; slot
for Network Management Card
options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
external battery packs
Hardwire input (4 wire split
phase); L6-30R, C19 & 5-15/20R
outlets
Package Includes
SU12000RT4UPM 4u UPS
Power Module
BP192V18-4U External battery
pack
SUPDMB16K Detachable PDU
with manual bypass switch
4 post rackmount installation
brackets
1 / 6
Dual conversion UPS actively converts raw input from AC to DC, then back to perfect sine wave AC output with enhanced protection from harmonic
distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types
Hardwire input terminals and output receptacles are mounted on a detachable back plate with manual bypass switch to enable hot-swappable UPS
replacement without powering off connected equipment
Provides perfectly regulated, sine wave output power free of line noise, transient surges and frequency variation for the most efficient operation of critical
servers, networking and telecommunications equipment
Maintains output within 3% of selected 208/120 or 240/120V nominal voltage during brownouts and overvoltages
Supports connected equipment during blackouts for 20/7 minutes at half/full load levels, runtime is further expandable with optional external
BP192V18-4U battery packs
Some external battery configurations require the use of Tripp Lite’s External Battery Configuration Software (see manual)
Intelligent battery management system extends battery life
Network interfaces support simultaneous communications via DB9 port, USB port and slot for network management card option
Compatible with Tripp Lite UPS management card options WEBCARDLX, SNMPWEBCARD, MODBUSCARD and RELAYIOCARD
DB9 port supports RS-232 and dry contact messaging. HID-compliant USB interface enables integration with built-in power management and auto
shutdown features of Windows and Mac OS X.
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite’s PowerAlert software, available via FREE download from
www.tripplite.com/poweralert
Built-in Emergency Power Off (EPO) interface with cable
Includes 13 output receptacles (2 L6-30R, 6 C19, 5 NEMA 5-15/20R) plus hardwire output, all of which are available for simultaneous use
Split phase, 4 conductor hardwire input connection (featured on included detachable PDU).
Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical conditions
Front panel switches enable power on/off control, self-test and alarm cancel functions
Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures
Optional 2-9USTAND set of tower stands supports upright tower installation
Optional 2POSTRMKITHD enables installation in 2 post racks (2 required)
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
$250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 12000
Output kVA Capacity (kVA) 12
Output Watt Capacity (Watts) 8400
Output kW Capacity (kW) 8.4
Output Capacity Details
12,000VA, 8400W (240V) / 10,395VA, 8400W (208V); Supports up to 105% load continuously in double conversion
mode, 106 to 125% for 3 minutes, 126 to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode
operation to support equipment directly from mains power; Double conversion mode is automatically restored as
the overload is cleared
Power Factor 0.7
Crest Factor 3:1
Nominal Output Voltage(s)
Supported 120V; 208V; 240V
2 / 6
Nominal Voltage Details 240/120V or 208/120V split phase output
Frequency Compatibility 60 Hz
Output Voltage Regulation (Line
Mode) +/- 3%
Output Voltage Regulation
(Economy Line Mode) +/- 10%
Output Voltage Regulation (Battery
Mode) +/- 3%
Output Receptacles (5) 5-15/20R; (2) L6-30R; (6) C19; Hardwire
Output Receptacle Details Supports North American 208/120V or 240/120V split-phase hardwire output (L1, L2, N, G)
Output Circuit Breakers 20A branch rated double pole breakers (x3) protect 2 C19 and 1 5-15/20R outlets each, 30A branch rated double
pole breakers (x2) protect 1 L6-30R outlet each, 20A single pole breakers (x2) protect one 5-15/20R outlet each
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 50A
Nominal Input Voltage(s) Supported 120/208V (Split phase L1,L2,N,G); 120/240V (Split phase L1,L2,N,G)
UPS Input Connection Type Hardwire
UPS Input Connection Description 4 wire split-phase input (L1, L2, N, G)
Recommended Electrical Service 50A 208/240-120 Split Phase (L1, L2, N, G); 6 AWG wiring recommended
Input Phase Single-Phase
BATTERY
Full Load Runtime (min.) 7 min. (8400w)
Half Load Runtime (min.) 20 min. (4200w)
Expandable Battery Runtime Supports extended runtime with optional external battery packs
External Battery Pack Compatibility BP192V18-4U; BP192V557C-16K; BP192V787C-16K; BP192V1037C-16K; BP192V1407C-16K
DC System Voltage (VDC) 192
Battery Recharge Rate (Included
Batteries) Less than 6 hours from 10% to 80% (typical, full load discharge)
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description +/-3% output voltage regulation in online, double-conversion mode
Overvoltage Correction Corrects overvoltages to 140 (measured L1-N : L2-N)
Undervoltage Correction Corrects undervoltages to 65V (measured L1-N : L2-N)
3 / 6
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module
replacement
Alarm Cancel Operation Alarm cancel switch
Audible Alarm Unique audible alarms for all major UPS, environmental and power conditions (see manual)
LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
SURGE / NOISE SUPPRESSION
UPS AC Suppression Response
Time Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description 2 sets of adjustable 4 post rack rails included
Installation Form Factors Supported
with Included Accessories 4 post 19 inch rackmount
Installation Form Factors Supported
with Optional Accessories 2 post rackmount(2POSTRMKITHD); Tower(2-9USTAND)
Optional Mounting Accessory Notes 2 sets of 2POSTRMKITHD required for 2 post rackmount installation
Primary Form Factor Rackmount
UPS Power Module Dimensions
(hwd, in.) 7 x 17.5 x 27.8
UPS Power Module Dimensions
(hwd, cm) 17.78 x 44.45 x 70.61
Rack Height (U Spaces) 8
Maximum Device Depth (in.) 34
Minimum Required Rack Depth
(inches) 40
Maximum Device Depth (cm) 86.36
Minimum Required Rack Depth (cm) 101.60
UPS Power Module Weight (lbs.) 86
UPS Power Module Weight (kg) 39.01
UPS Dimensions Details Includes 4U battery pack, 4U UPS/power module and detachable bypass PDU; MAXIMUM DEVICE DEPTH
specification refers to the whole UPS installed depth with bypass PDU installed
Included Battery Pack Dimensions
(hwd / in.) 7 x 17.5 x 27.8
4 / 6
Included Battery Pack Weight (lbs.) 239
Included Battery Pack Weight (kg) 108.41
UPS Shipping Dimensions (hwd / in.) 45.5 x 23.5 x 34.3
UPS Shipping Dimensions (hwd /
cm) 115.57 x 59.69 x 87.12
Shipping Weight (lbs.) 448.8
Shipping Weight (kg) 203.8
Cooling Method Fan
UPS Housing Material Steel
Maximum Device Depth (mm) 864
Minimum Required Rack Depth (mm) 1016
Primary UPS Height (mm) 178
Primary UPS Width (mm) 444
Primary UPS Depth (mm) 706
Shipping Height (mm) 1156
Shipping Width (mm) 597
Shipping Depth (mm) 871
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 4286
AC Economy Mode BTU / Hr. (Full
Load) 1829
Battery Mode BTU / Hr. (Full Load) 3187
AC Mode Efficiency Rating (100%
Load) 87%
AC Economy Mode Efficiency Rating
(100% Load) 94%
Operating Elevation (ft.) 0-3000m (0 to 10,000 ft.)
Audible Noise 60 dBA at front side 1 meter
Operating Elevation (m) 0-3000 m
COMMUNICATIONS
Communications Interface USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network Management Cards SNMPWEBCARD; WEBCARDLX; MODBUSCARD; RELAYIOCARD
5 / 6
Network Monitoring Port Description RS232 and contact closure communications are supported on one DB9 port
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://www.tripplite.com/poweralert
Communications Cable USB and DB9 cabling included
LINE / BATTERY TRANSFER
Transfer Time No transfer time (0 ms.) in online, double-conversion mode
Transfer Time (Economy Mode) 2 milliseconds typical in optional economy mode
Low Voltage Transfer to Battery
Power (Setpoint) 65V (L1-N:L2-N)
High Voltage Transfer to Battery
Power (Setpoint) 140V (L1-N:L2-N)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure) Cold-start operation supported
High Availability UPS Features Automatic inverter bypass; Hot swappable batteries; Hot swappable UPS power module; Manual bypass switch
Green Energy-Saving Features High efficiency economy mode operation; Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
WARRANTY
Product Warranty Period (Worldwide) 2-year limited warranty
Connected Equipment Insurance
(U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance

Additional information

Weight 203.57 kg
Dimensions 93.98 × 60.96 × 85.09 cm
Brand