Sale!
	
	
		
	
            
			
	
	
	
Compare
	
	
	
		
					
				
	
			
					
				
	
			
			
		
			
	
	
			$57,820.68
SmartOnline SVX Series 30kVA 400/230V 50/60Hz Modular Scalable 3-Phase On-Line Double-Conversion Medium-Frame UPS System, 5 Battery Modules
Description
Specifications
OVERVIEW
| UPC Code | 037332206039 | 
| UPS Type | On-Line | 
INPUT
| Rated input current (Maximum Load) | 30kVA Configuration: 55A; Maximum 90kVA N+1 Medium Chassis Configuration: 165A; 40A maximum inrush current | 
| Nominal Input Voltage(s) Supported | 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye | 
| Nominal Input Voltage Description | Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, E) inputs from two separate power sources | 
| UPS Input Connection Type | Hardwire | 
| Input Circuit Breakers | MAIN and ALTERNATE AC inputs are each protected by 400A 3 pole magnetic breakers | 
| Input Phase | 3-Phase | 
| Input Frequency | 40 to 70Hz (online mode); 50/60Hz Auto-selectable | 
| Power Factor (Input) | Greater than 0.99 (full load) | 
| THDi | Less than 3% (full linear load) | 
OUTPUT
| Output Volt Amp Capacity (VA) | 30000 | 
| Output Capacity (kVA) | 30 | 
| Output Watt Capacity (Watts) | 30000 | 
| Output kW Capacity (kW) | 30 | 
| Output Capacity Details | OVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1 minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to 100% or less | 
| Power Factor | 1.0 | 
| Crest Factor | 3:1 | 
| Nominal Voltage Details | Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included | 
| Frequency Compatibility | 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion | 
| Frequency Compatibility Details | Auto-selectable, user adjustable | 
| Output Receptacle Details | Output wiring (3P, N, E) | 
| Output Circuit Breakers | 400A 3 pole magnetic breaker | 
| Output AC Waveform (AC Mode) | Pure Sine wave | 
| Output AC Waveform (Battery Mode) | Pure Sine wave | 
| Nominal Output Voltage(s) Supported | 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye | 
| Output Receptacles | Hardwire | 
| Output Voltage Regulation | ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 220/230/240V ±1% typical (balanced load); ±2% typical (unbalanced load); ECONOMY MODE: 220/230/240V ±15V; BYPASS MODE: +15% (default, adjustable to +10%, +15% or +20%), -20% (default, adjustable to -10%, -20%, -30%) | 
| Output Frequency Regulation | ONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured 50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside ±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances as described above in Online, Economy and Bypass modes | 
| Output Amp Capacity | 45.6A (220/380V); 43.3A (230/400V); 41.7A (240/415V) | 
| Individually Controllable Load Banks | No | 
| Modular Upgrade Options | Includes 1 SVX30PM 30kVA power module; Up to 3 additional SVX30PM 30kVA power modules can be added for additional capacity or N+1 availability; Add 1 SVX30PM for 60kVA capacity (or 30kVA with N+1 redundancy); Add 2 SVX30PM for 90kVA capacity (or 60kVA with N+1 redundancy); Add 3 SVX30PM for 90kVA capacity with N+1 redundancy | 
BATTERY
| Full Load Runtime (min.) | 4.7 minutes (30kW) | 
| Half Load Runtime (min.) | 11 minutes (15kW) | 
| Expandable Battery Runtime | Supports extended runtime with optional external battery packs; 100A 3 pole 250VDC breaker recommended for external battery | 
| Expandable Runtime | Yes | 
| Expandable Runtime Description | External battery pack wiring is contractor supplied; All external battery configurations require the disconnection of internal battery modules | 
| External Battery Pack Compatibility | BP480V200 ; BP480V300 ; BP480V400 ; BP480V500 ; BP480V370 | 
| DC System Voltage (VDC) | ±240VDC | 
| Battery Recharge Rate (Included Batteries) | User selectable charging current of 1A to 8A (2A factory setting); Recharge rate is dependent on number of external battery packs connected and the selected charge current setting | 
| Battery Replacement Description | Hot-swappable, replaceable batteries | 
VOLTAGE REGULATION
| Voltage Regulation Description | Online, double-conversion power conditioning | 
| Overvoltage Correction | Maintains continuous output in online mode, without using battery power, during overvoltages to 478V (Ph-Ph), reducing output to within 1% of selected 380/220V, 400/230V, 415/240V nominal output voltage | 
| Undervoltage Correction | Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions to 305V (Ph-Ph) at full load and to 208V (Ph-Ph) at 70% output load or less, increasing output to within 1% of selected 380/220V, 400/230V, 415/240V nominal output voltage | 
USER INTERFACE, ALERTS & CONTROLS
| Front Panel LCD Display | 145mm front panel LCD display with directional scroll and select buttons offers complete operating status display, plus setting and selection options for all UPS functions | 
| Switches | Front panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right), ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes Manual Bypass switch | 
| Alarm Cancel Operation | Audible alarms can be muted using on-screen prompts | 
| Audible Alarm | Unique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1 second), UPS FAULT (continuous alarm) | 
| LED Indicators | Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and ALARM (red) | 
SURGE / NOISE SUPPRESSION
| EMI / RFI AC Noise Suppression | Yes | 
| AC Suppression Joule Rating | 2496 | 
| AC Suppression Joule Rating Details | 2496 joules (Ph-E), 2496 joules (Ph-N), 1872 joules (N-E) | 
| AC Suppression Response Time | Instantaneous | 
PHYSICAL
| Primary Form Factor | Tower | 
| Cooling Method | Fans | 
| Installation Form Factors Supported with Included Accessories | Tower | 
| Primary UPS Depth (mm) | 1,100 | 
| Primary UPS Height (mm) | 2,010 | 
| Primary UPS Width (mm) | 600 | 
| Shipping Dimensions (hwd / in.) | 85.62 x 29.52 x 48.03 | 
| Shipping Weight (lbs.) | 1058.00 | 
| UPS Housing Material | Steel | 
| UPS Power Module Dimensions (hwd, in.) | 79.13 x 23.62 x 43.3 | 
| UPS Power Module Weight (kg) | 516.64 | 
| UPS Power Module Weight (lbs.) | 1139 | 
ENVIRONMENTAL
| Operating Temperature Range | 0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F | 
| Storage Temperature Range | -15° to +60°C (+5° to +140°F) | 
| Relative Humidity | 0 to 95%, non-condensing | 
| AC Mode BTU / Hr. (Full Load) | 5615 | 
| AC Economy Mode BTU / Hr. (Full Load) | 711 | 
| AC Mode Efficiency Rating (100% Load) | 95% | 
| AC Economy Mode Efficiency Rating (100% Load) | 99% | 
| Audible Noise | Less than 73 DBA front-side, 1m | 
| Operating Elevation (m) | Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m) | 
COMMUNICATIONS
| Network Management Cards | WEBCARDLX ; MODBUSCARDSV ; RELAYCARDSV | 
| Network Monitoring Port Description | Includes pre-installed Tripp Lite WEBCARDLX network interface | 
| PowerAlert Software | For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert | 
| Communications Cable | DB9 cabling included | 
| SNMP Compatibility | Includes pre-installed WEBCARDLX network interface card | 
| Communications Interface | DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface | 
LINE / BATTERY TRANSFER
| Transfer Time | No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode | 
| Low Voltage Transfer to Battery Power (Setpoint) | Maintains continuous operation without using battery power during brownout/undervoltage conditions to 305V (Ph-Ph) Full load or 208V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained utilizing reserve battery power | 
| High Voltage Transfer to Battery Power (Setpoint) | Maintains continuous operation without using battery power during overvoltages to 478V (Ph-Ph), reducing output within 1% of nominal; Above this point, output is maintained utilizing reserve battery power | 
FEATURES & SPECIFICATIONS
| Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported | 
| High Availability UPS Features | Automatic inverter bypass; Hot swappable batteries; Auto Probe Monitoring (included); Zero transfer time; On-Line/Double-Conversion | 
| Green Energy-Saving Features | Greater than 95% efficiency – GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of economy mode operation | 
| IP68 Rated | Yes | 
STANDARDS & COMPLIANCE
| Product Certifications | UL Listed | 
| Product Compliance | RoHS; CE (Europe); REACH | 
WARRANTY & SUPPORT
| Product Warranty Period (International) | 2-year limited warranty | 
| 3-Phase Warranty Statement | Tripp Lite 3-Phase UPS Factory Warranty | 
Additional information
| Brand | 
|---|