Description
Tripp Lite’s SVX90KM3P5B 90kVA/90kW SmartOnline® Medium-Frame UPS includes installed input, bypass
and output breakers, a static transfer switch (STS) and 3 included 30kVA SVX30PM power modules. This
system supports the addition of 1 additional user-installable SVX30PM power module to accommodate 90kW
total capacity with N+1 fault-tolerance. Five internal battery modules are included to fully load internal battery
compartments. Additional runtime is available using any number of compatible ±240VDC external battery packs
(sold separately).
Featuring a modular, scalable design with high-efficiency voltage and frequency independent/VFI operation,
Tripp Lite’s SVX Series SmartOnline UPS systems are ideal for the protection of a wide variety of critical IT
systems. Scalable, modular configuration enables UPS capacity upgrades and hot-swap power supply
maintenance without costly downtime. Over 95% efficient in standard online mode and over 99% efficient in
optional economy mode enables reduced operating and cooling costs. Unity power factor configuration provides equal kVA and kW output ratings for up to
25% more wattage capacity than common 0.8 – 0.9 power factor competing designs. Network-grade sine-wave AC output with 1% output voltage regulation
and less than 1.5% output total harmonic distortion. Advanced IGBT inverter with Digital Signal Processor (DSP) technology provides for less than 3% input
total harmonic distortion (THDi) to support 1:1 generator sizing. Dual-input hardwire design enables operation from one or two input power sources for
enhanced system availability. N+1 fault-tolerance is configurable anytime there is an “extra” SVX30PM 30kW power module installed beyond the minimum
required quantity. Automatic and manual bypass options keep connected equipment operational during routine maintenance or critical power module failure.
Features
Tripp Lite’s SVX90KM3P5B 90kVA/90kW SmartOnline UPS offers network-grade power protection in a highly configurable medium-frame modular,
scalable form factor
Includes 3 SVX30PM 30kW power modules for 90kVA total capacity; Open slots for 1 additional SVX30PM 30kW power module enable enhanced N+1
Highlights
90kVA/90kW Modular, Scalable,
3-Phase Medium-Frame Tower
UPS
Supports 3-Phase 220/380V,
230/400V or 240/415V AC,
50/60Hz, Wye
Scalable configuration with option
to upgrade to add N+1
redundancy
High-Efficiency On-Line UPS
with DSP/IGBT Technology and
1% Output Voltage Regulation
Economy-Mode option further
reduces operating and cooling
costs
Pre-installed WEBCARDLX
network interface
Tested to CE for worldwide
applications
Includes 5 internal battery
modules; External battery
options available
Package Includes
SVX90KM3P5B Medium-Frame
Modular UPS System
(3) SVX30PM 30kVA power
modules
(5) SVXBM battery modules
Pre-installed WEBCARDLX
network interface
Owner’s manual
1 / 6
redundancy
Included batteries support a full load of 90kW for 4.2 minutes and half load of 45kW for 8.8 minutes; Extended runtime is available with the addition of any
number of supported external battery packs (sold separately)
Supports 220/380, 230/400 or 240/415V AC, 3-Phase Wye 4-Wire plus Earth Hardwire input and output wiring
Tested to CE for worldwide applications
Pre-installed WEBCARDLX network interface
Serial port enables unattended shutdown and UPS monitoring ability
Modular configuration with hot-swappable power modules enables easy and fast maintenance with zero downtime
Wide input voltage operating range enables full continuous online operation during brownouts as low as 120V (Ph-N) and overvoltages up to 276 (Ph-N)
Narrow output voltage operating range regulates output voltage within 1% of the selected 220/230/240 nominal output voltage in online,
double-conversion mode
Over 95% efficient in online, double-conversion mode and over 99% efficient in optional economy-mode enables reduced operating and cooling costs
Less than 3% input Total Harmonic Distortion (THDi) prevents the need to oversize generator systems relative to UPS capacity
Dual hardwire input design enables operation from one or two input power sources
Front panel combination LCD/LED display offers full UPS condition and status reporting plus additional configuration options
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 90000
Output kVA Capacity (kVA) 90
Output Watt Capacity (Watts) 90000
Output kW Capacity (kW) 90
Output Capacity Details
OVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1
minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to
100% or less
Power Factor 1.0
Crest Factor 3:1
Nominal Output Voltage(s)
Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
Nominal Voltage Details Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle
deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details Auto-selectable, user adjustable
Output Receptacles Hardwire
Output Receptacle Details Output wiring: 3P, N, E
Output Circuit Breakers 400A 3 pole magnetic breaker
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
2 / 6
Output Voltage Regulation
ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 220/230/240V ±1% typical (balanced load); ±2% typical
(unbalanced load); ECONOMY MODE: 220/230/240V ±15V; BYPASS MODE: +15% (default, adjustable to +10%,
+15% or +20%), -20% (default, adjustable to -10%, -20%, -30%)
Output Frequency Regulation
ONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured
50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside
±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured
50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz
output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz
output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output
frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY
mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user
adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances
as described above in Online, Economy and Bypass modes
Output Amp Capacity 137A (220/380V); 130A (230/400V); 125A (240/415V)
Modular Upgrade Options Includes 3 SVX30PM 30kVA power modules; 1 additional SVX30PM 30kVA power module can be added for N+1
availability; Add 1 SVX30PM for 90kVA capacity with N+1 redundancy
INPUT
Rated input current (Maximum Load) 110A Maximum
Nominal Input Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
Nominal Input Voltage Description Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, G) inputs from two separate power
sources
UPS Input Connection Type Hardwire
Input Circuit Breakers MAIN and ALTERNATE AC inputs are each protected by 400A 3 pole magnetic breakers
Input Phase 3-Phase
Input Frequency 40 to 70Hz (online mode); 50/60Hz Auto-selectable
Power Factor (Input) Greater than 0.99 (full load)
THDi Less than 3% (full linear load)
BATTERY
Full Load Runtime (min.) 4.2 minutes (90kW)
Half Load Runtime (min.) 8.8 minutes (45kW)
Expandable Battery Runtime Supports extended runtime with optional external battery packs; 100A 3 pole 250VDC breaker recommended for
external battery
External Battery Pack Compatibility BP480V200; BP480V300; BP480V400; BP480V500; BP480V370
Expandable Runtime Description External battery pack wiring is contractor supplied; All external battery configurations require the disconnection of
internal battery modules
DC System Voltage (VDC) ±240VDC
Battery Recharge Rate (Included
Batteries)
User selectable charging current of 1A to 8A (2A factory setting); Recharge rate is dependent on number of external
battery packs connected and the selected charge current setting
Battery Replacement Description Hot-swappable, replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
3 / 6
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction Maintains continuous output in online mode, without using battery power, during overvoltages to 478V (Ph-Ph),
reducing output to within 1% of selected 380/220V, 400/230V, 415/240V nominal output voltage
Undervoltage Correction
Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions
to 305V (Ph-Ph) at full load and to 208V (Ph-Ph) at 70% output load or less, increasing output to within 1% of
selected 380/220V, 400/230V, 415/240V nominal output voltage
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display 145mm front panel LCD display with directional scroll and select buttons offers complete operating status display,
plus setting and selection options for all UPS functions
Switches
Front panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right),
ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes
Manual Bypass switch
Alarm Cancel Operation Audible alarms can be muted using on-screen prompts
Audible Alarm
Unique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm
sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1
second), UPS FAULT (continuous alarm)
LED Indicators Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and
ALARM (red)
SURGE / NOISE SUPPRESSION
EMI / RFI AC Noise Suppression Yes
AC Suppression Joule Rating 2496
AC Suppression Joule Rating Details 2496 joules (Ph-Ph), 2496 joules (Ph-N), 1872 joules (N-E)
AC Suppression Response Time Instantaneous
PHYSICAL
Installation Form Factors Supported
with Included Accessories Tower
Primary Form Factor Tower
UPS Power Module Dimensions
(hwd, in.) 79.13 x 23.62 x 43.3
UPS Power Module Dimensions
(hwd, cm) 200.99 x 59.99 x 109.98
Maximum Device Depth (cm) 0
UPS Power Module Weight (lbs.) 1979
UPS Power Module Weight (kg) 897.66
UPS Shipping Dimensions (hwd / in.) 85.62 x 29.52 x 48.03
UPS Shipping Dimensions (hwd /
cm) 217.47 x 74.98 x 122.00
Shipping Weight (lbs.) 2215
Shipping Weight (kg) 1005
4 / 6
Cooling Method Fans
UPS Housing Material Steel
Primary UPS Height (mm) 2010
Primary UPS Width (mm) 600
Primary UPS Depth (mm) 1100
Shipping Height (mm) 2175
Shipping Width (mm) 750
Shipping Depth (mm) 1220
ENVIRONMENTAL
Operating Temperature Range 0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F
Storage Temperature Range -15° to +60°C (+5° to +140°F)
Relative Humidity 0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load) 17200
AC Economy Mode BTU / Hr. (Full
Load) 3100
AC Mode Efficiency Rating (100%
Load) 95%
AC Economy Mode Efficiency Rating
(100% Load) 99%
Audible Noise Less than 73 DBA front-side, 1m
Operating Elevation (m) Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m)
COMMUNICATIONS
Communications Interface DB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface
Network Management Cards WEBCARDLX
Network Monitoring Port Description Includes pre-installed Tripp Lite WEBCARDLX network interface
PowerAlert Software For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://www.tripplite.com/poweralert
Communications Cable DB9 cabling included
SNMP Compatibility Includes pre-installed WEBCARDLX network interface card
LINE / BATTERY TRANSFER
Transfer Time No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode
Low Voltage Transfer to Battery
Power (Setpoint)
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 305V
(Ph-Ph) Full load or 208V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained
utilizing reserve battery power
High Voltage Transfer to Battery
Power (Setpoint)
Maintains continuous operation without using battery power during overvoltages to 478V (Ph-Ph), reducing output
within 1% of nominal; Above this point, output is maintained utilizing reserve battery power
5 / 6
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure) Cold-start operation supported
High Availability UPS Features Automatic inverter bypass; Hot swappable batteries
Green Energy-Saving Features Greater than 95% efficiency – GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of
economy mode operation
CERTIFICATIONS
UPS Certifications CE; ROHS (Restriction of Hazardous Substances)
UPS Certification Details Agency standards IEC 62040-1:2008+A1:2013; EMI Approvals EN62040-2, 2006 (Category C3); Vibration and
Shock: SS-EN 60068-2-64
WARRANTY
Product Warranty Period
(International) 2-year limited warranty

Additional information