OVERVIEW
| UPC Code | 037332157140 |
| UPS Type | On-Line |
INPUT
| Rated input current (Maximum Load) | 24A (208V) |
| Nominal Input Voltage(s) Supported | 208V AC |
| UPS Input Connection Type | L6-30P |
| UPS Input Cord Length (ft.) | 10 |
| Recommended Electrical Service | 30A |
| Input Phase | Single-Phase |
OUTPUT
| Output Volt Amp Capacity (VA) | 5000 |
| Output Capacity (kVA) | 5.0 |
| Output Watt Capacity (Watts) | 4500 |
| Output kW Capacity (kW) | 4.5 |
| Output Capacity Details | Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as the overload is cleared |
| Power Factor | 0.9 |
| Crest Factor | 3:1 |
| Nominal Voltage Details | 208V default power module setting; This configuration requires the Power Module be set to 208V output voltage; Included step-down transformer supports 120V output |
| Frequency Compatibility | 60 Hz |
| Frequency Compatibility Details | Output frequency regulation +/- 0.05Hz (free running) |
| Output Voltage Regulation (Line Mode) | +/- 2% |
| Output Voltage Regulation (Economy Line Mode) | +/- 10% |
| Output Voltage Regulation (Battery Mode) | +/- 2% |
| Output Circuit Breakers | High voltage 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered; Low voltage 20A breakers protect 3 5-15/20R outlets each |
| Output AC Waveform (AC Mode) | Pure sine wave |
| Output AC Waveform (Battery Mode) | Pure Sine wave |
| Nominal Output Voltage(s) Supported | 120V; 208V |
| Output Receptacles | (12) 5-15/20R; (2) L6-20R; (2) L6-30R |
| Individually Controllable Load Banks | No |
BATTERY
| Battery Type | Valve Regulated Lead Acid (VRLA) |
| Full Load Runtime (min.) | 3.5 minutes (4500w) |
| Half Load Runtime (min.) | 11 minutes (2250w) |
| Expandable Battery Runtime | Supports extended runtime with optional external battery packs |
| Expandable Runtime | Yes |
| External Battery Pack Compatibility | BP192V12-3U ; BP192V5RT2U (limit 1); BP192V787C-1PH |
| DC System Voltage (VDC) | 192 |
| Battery Recharge Rate (Included Batteries) | 6 hours from 10% to 90% (typical, full load discharge) |
| Battery Access | Front panel battery access door |
| Internal UPS Replacement Battery Cartridge | RBC5-192 (qty 1) |
| Battery Replacement Description | Hot-swappable, user replaceable batteries |
VOLTAGE REGULATION
| Voltage Regulation Description | Online, double-conversion power conditioning |
| Overvoltage Correction | 2% output voltage regulation during overvoltages to 280V (full load) / 300V (90% load or less) |
| Undervoltage Correction | 2% output voltage regulation during undervoltages to 156V (full load) / 100V (50% load or less) |
USER INTERFACE, ALERTS & CONTROLS
| Front Panel LCD Display | Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats (see manual) |
| Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions |
| Alarm Cancel Operation | Alarm cancel switch |
| Audible Alarm | Unique audible alarms for all major UPS, environmental and power conditions (see manual) |
| LED Indicators | 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options |
SURGE / NOISE SUPPRESSION
| UPS AC Suppression Joule Rating | 2595 |
| UPS AC Suppression Response Time | Instantaneous |
| EMI / RFI AC Noise Suppression | Yes |
PHYSICAL
| Primary Form Factor | Rackmount |
| Rack Height | 6U |
| Cooling Method | Fan |
| Included Mounting Accessory Description | 2 sets of adjustable 4 post rack rails included |
| Installation Form Factors Supported with Included Accessories | 4 post 19 inch rackmount |
| Installation Form Factors Supported with Optional Accessories | 2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND ) |
| Maximum Device Depth (in.) | 20.75 |
| Minimum Required Rack Depth with External Battery Pack (cm) | 74 |
| Minimum Required Rack Depth with External Battery Pack (in.) | 29 |
| Minimum Required Rack Depth without External Battery Pack (cm) | 65 |
| Minimum Required Rack Depth without External Battery Pack (in.) | 25.75 |
| Optional Mounting Accessory Notes | 2 sets of 2POSTRMKITHD required for 2 post rackmount installation of separate 4U power module and 2U transformer |
| Primary UPS Depth (mm) | 525 |
| Primary UPS Height (mm) | 174 |
| Primary UPS Width (mm) | 445 |
| Shipping Dimensions (hwd / in.) | 22.20 x 23.60 x 29.10 |
| Shipping Weight (lbs.) | 227.80 |
| Stepdown Transformer Dimensions (hwd / in.) | 3.5 x 17.5 x 20.75 |
| Stepdown Transformer Height (mm) | 89 |
| Stepdown Transformer Width (mm) | 445 |
| Stepdown Transformer Depth (mm) | 527 |
| Stepdown Transformer Weight (lbs.) | 76 |
| UPS Housing Material | Sheet metal |
| UPS Power Module Dimensions (hwd, in.) | 6.85 x 17.5 x 20.67 |
| UPS Power Module Weight (kg) | 51.53 |
| UPS Power Module Weight (lbs.) | 113.6 |
ENVIRONMENTAL
| Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
| Storage Temperature Range | 5 to 122 F / -15 to 50 C |
| Relative Humidity | 5% to 90% (non-condensing) |
| AC Mode BTU / Hr. (Full Load) | 1767 |
| AC Economy Mode BTU / Hr. (Full Load) | 640 |
| Battery Mode BTU / Hr. (Full Load) | 1708 |
| AC Mode Efficiency Rating (100% Load) | 90% |
| AC Economy Mode Efficiency Rating (100% Load) | 96% |
| Operating Elevation (ft.) | 0 to 6560 ft. / 0 to 2000 m |
| Audible Noise | 65 dB at 1m front side |
| Operating Elevation (m) | 0-2000 m |
COMMUNICATIONS
| Network Management Cards | SNMPWEBCARD; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD |
| Network Monitoring Port Description | Two contact closure monitoring options available – RELAYIOCARD with six configurable contact closure outputs (uses UPS card slot) and RELAYIOMINI with 3 configurable contact closure outputs (requires removal of USB port module) |
| PowerAlert Software | For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert |
| Communications Cable | USB, DB9 serial and EPO cables included |
| WatchDog Compatibility | Yes |
| Network Management Card Description | Network management card optional |
| Communications Interface | DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |
LINE / BATTERY TRANSFER
| Transfer Time | No transfer time (0 ms.) in online, double-conversion mode |
| Low Voltage Transfer to Battery Power (Setpoint) | 156V (full load) / 100V (50% load or less, derates linearly) |
| High Voltage Transfer to Battery Power (Setpoint) | 280V (full load) / 300V (90% load or less) |
FEATURES & SPECIFICATIONS
| Cold Start (Startup in Battery Mode During a Power Failure) | Cold-start operation supported |
| High Availability UPS Features | Auto Probe Monitoring (requires WEBCARDLX); Automatic inverter bypass; Expandable battery backup; Hot swappable batteries; On-Line/Double-Conversion; Remote management; Sine wave output; Surge/noise protection; Zero transfer time |
| Green Energy-Saving Features | High efficiency economy mode operation; Support for daily startup and shutoff; Schedulable daily hours of economy mode operation |
STANDARDS & COMPLIANCE
| Product Certifications | IEC 61000; CSA (Canada); UL 1778 |
| Product Compliance | RoHS; FCC Part 15 Class B (USA) |
WARRANTY & SUPPORT
| Product Warranty Period (Worldwide) | 2-year limited warranty |
| Connected Equipment Insurance (U.S., Canada & Puerto Rico) | $250,000 Ultimate Lifetime Insurance |
Additional information
| Weight | 103.32 kg |
|---|---|
| Dimensions | 56.38 × 59.94 × 73.91 cm |
| Brand |